Matt Fulford visited the school, and in agreement with the school reset the controls as follows:
- Dining and Hall Heating; was running 24/7, this has now been reset to 5am to 4.30pm on Monday and 6am to 4.30pm Tuesday to Friday and off on Saturday and Sunday. The set point has been dropped from 22 degrees to 19 degrees.
- The Hot Water has been reset from 5.30am to 5pm each weekday to 5am to 4.30pm on Monday (to give extra pasteurisation time at the start of the week) and from 6am to 4.30pm Tuesday to Friday and it continues to remain off at the weekend. This is to align better to the schools times and has been considered carefully against a review of the hot water temperature logs to check the warm up times.
- The secondary stage frost (return pipe sensor) has been reset from 25 degrees to 12 degrees which remains well above freezing conditions but is more in line with the natural temperature of mains cold water.
- The indoor eco hold off temperature has been reduced from 25 degrees to 21 degrees to help avoid overheating experienced in the school.